 |
Multi-Transducer 1 analog SINEAX M561
•
1 analogue output
•
Application ( system ) programmable
• Rated
current 1 to 6A programmable
•
Rated voltage 57 to 400V ( phase-to-neutal ) or 100 to 693 V
( phase to phase ) programmable
•
Universal analogue output ( programmable )
•
High accuracy: class 0.5
•
Software with password protection for programming, data analysis,
power
system status simulation acquisition of meter data amd making
settinge
•
DC, AC power pack with verv large tolerance range
•
Mounting: For snapping onto top-hat rail
• CSA
certificate
<<ÃÒÂÅÐàÍÕ´>> |
 |
Multi-Transducer 2 analog SINEAX M562
•
2 analogue output
•
Application ( system ) programmable
• Rated
current 1 to 6A programmable
•
Rated voltage 57 to 400V ( phase-to-neutal ) or 100 to 693 V
( phase to phase ) programmable
•
Universal analogue output ( programmable )
•
High accuracy: class 0.5
•
Software with password protection for programming, data analysis,
power
system status simulation acquisition of meter data amd making
settinge
•
DC, AC power pack with verv large tolerance range
•
Mounting: For snapping onto top-hat rail
• CSA
certificate
<<ÃÒÂÅÐàÍÕ´>> |
 |
Multi-Transducer 3 analog SINEAX M563
•
3 analogue output
•
Application ( system ) programmable
• Rated
current 1 to 6A programmable
•
Rated voltage 57 to 400V ( phase-to-neutal ) or 100 to 693 V
( phase to phase ) programmable
•
Universal analogue output ( programmable )
•
High accuracy: class 0.5
•
Software with password protection for programming, data analysis,
power
system status simulation acquisition of meter data amd making
settinge
•
DC, AC power pack with verv large tolerance range
•
Mounting: For snapping onto top-hat rail
• CSA
certificate
<<ÃÒÂÅÐàÍÕ´>> |
 |
AC current Transducer SINEAX
i542
•
Measurement method: Rectifier process
•
Measurement input: Alternating current, sinusoidal, arithmetic mean
value
measurement effective value calibration
•
Measuring range: 1/5A or 1.2/6A selectsble terminals
•
Measurement output: Unipolar 0...1, 0...5, 0...10 or 0...20 mA
•
or 0...1 to 0...10 V
•
Power supplay: without power supply terminal ( self-powered )
less wiring expense
•
Standard as marind as marine version per LIoyd"s Register of
Shipping
•
P8/35 housing for top-hat rail mounting
• CSA
certificate German Lloyd approval
<<ÃÒÂÅÐàÍÕ´>> |
 |
AC current
transducer SINEAX i538
•
Measurement method: Rectifier process
•
Measurement input: Alternating current, sinusoidal, arithmetic mean
value
measurement effective value calibration
•
Measuring range: 0.. 0.8 to 0.. 1.2A or 0..4 to 0..6 A
•
Measurement output: Unipolar and live-zero
0..1.0 to 0..20mA resp. live-Zero 0.2.. 1 to 4..20mA or
0..1 to 0..10V resp. live-zero 0.2..1 to 2..10V
•
Also available with power supply via output circuit at 2-wrie
connection
•
Power supply: AC or DC power supplay or
wide DC AC power pack tolerance
•
Standard as marine version per Lloyd's Register of Shipping
•
P8/35 housing for top-har rail mounting
•
CSA certifiacte German Lloyd approval
<<ÃÒÂÅÐàÍÕ´>>
|
 |
AC current
transducer SINEAX i552
•
Measurement method: Rectifier process
•
Measurement input: Alternating current, sinusoidal, or distorted
true
RMS value measurement
•
Measuring range: 1/5 or 1.2/6A selectable at terminals
•
Measurement output: unipolar and live-Zero
0...1.0 to 0.20 mA resp. live-zero 0.2...1 to 4..20 mA or
0...1 to 0...10 V resp. live-zero 0.2...1 to 2...10V
•
Power supply: wide DC,AC power pack
tolerance
•
Standard as marine version per Lloyd's Register of Shipping
•
P8/35 housing for top-har rail mounting
•
CSA certifiacte German Lloyd approval
<<ÃÒÂÅÐàÍÕ´>>
|
 |
AC Voltage
transducer U543
•
Measurement method: Rectifier process
•
Measurement input: Alternating volage, sinusoidal arithmetic mean
value measurement effective value calibration
•
Nominal input volatge: 0...20 to 0...600V
•
Measurement output: unipolar
0...1 ,0...5, 0...10 or 0...20mA or 0...1 to 0...10V
•
Power supply: without power supplay
terminal ( seft-powered )
less wiring expense
•
Standard as marine version per Llovd' s Register of Shipping
•
P8/35 housing for top-hat rail mounting
•
CSA certifiacte German Lloyd approval
<<ÃÒÂÅÐàÍÕ´>> |
 |
AC Voltage
transducer U539
•
Measurement method: Rectifier process
•
Measurement input: Alternating volage, sinusoidal arithmetic mean
value measurement effective value calibration
•
Measuring range limits: 0...50 to 0...600V
•
Measurement output: unipolar and live-zero
0...1.0 to 0.20 mA resp. live-zero 0.2...1 to 4...20 mA or
0...1 to 0...10 V resp.
live-zero 0.2...1 to 2...10V
•
Also available with power supplay via output circuit at 2-wire
connection
• Power
supplay: AC or DC power supplay or wide DC,AC power pack
tolerance
• Standard as marine version per Lloyd's Register of Shipping
•
P8/35 housing for top-har rail mounting
• CSA
certificate German Lloyd approval
<<ÃÒÂÅÐàÍÕ´>> |
 |
AC Voltage
transducer U553
•
Measurement method: Rectifier process
•
Measurement input: Alternating volage, sinusoidal or distorted true
RMS
value measurement
•
Nominal input volatge: 0...20 to 0...690V
•
Measurement output: unipolar nad live-zero
0...1.0 to 0.20 mA resp. live-zero 0.2...1 to 4...20 mA or
0...1 to 0...10 V resp.
live-zero 0.2...1 to 2...10V
•
power supplay wide DC,AC,power pack
tolerance
•
Standard as marine version per Llovd' s Register of Shipping
• P13/70 housing for top-hat rail mounting
• CSA certifiacte German Lloyd approval
<<ÃÒÂÅÐàÍÕ´>> |
 |
AC Voltage
transducer U554
•
Measurement method: logarithmic measuring method
•
Measurement input: sinusoidal or distorted alternating voltage TRMS
measurement Input voltage : 0..20 to 0.. 690 V
•
Measurement output: unipolar and live-zero output quantities
from 0... 1.0 to 0.20 mA or live-zero from 0.2.. 1 to
4..20mA , or
from 0... 1 to 0..10 V or live-
zero from 0.2.. 1 to 2.. 10V
•
Characteristics as expanded voltage voltage scale or expanded
primary
value scale at the lower or upper range
•
Power supplay: AC auxiliary power, or integrated AC-DC power pack
with large tolerance range
•
P13/70 housing for top-har rail mounting
<<ÃÒÂÅÐàÍÕ´>> |
 |
Measuring
transducer SINEAX P530
•
Measurement method: TDM method
•
Measurement input: sinusoidal nominal input current ( 1 or 5 A ) and
nominal input voltage ( 100 to 690 V )
•
Nominal input frequency: 50 Hz
•
Measuring range: 0 to 4 kW
•
Measurement output: unipolar: unipolar, bipolar or live-zero output
quantities
• Power supply: integrated
AC-DC power pack with large tolerance
range for universal use
•
Standard GL ( Germanischer Lioyd ) / suitable for use on ocean-going
vessels
•
Housings - top-hat rail mounting
P13/170 housing for single-phase alternationg current
P18/105 housing for 3-phase current
•
CSA certificate German Lloyd approval
<<ÃÒÂÅÐàÍÕ´>> |
 |
Measuring
transducer SINEAX Q531
•
Measurement method: TDM method
•
Measurement input: sinusoidal nominal input current ( 1 or 5 A ) and
nominal input voltage ( 100 to 690 V )
•
Nominal input frequency: 50 Hz
•
Measuring range: 0 to 2 kVar
•
Measurement output: unipolar: unipolar, bipolar or live-zero output
quantities
• Power supply: integrated
AC-DC power pack with large tolerance
range for universal use
•
Standard GL ( Germanischer Lioyd ) / suitable for use on ocean-going
vessels
•
Housings - top-hat rail mounting
P13/170 housing for single-phase alternationg current
P18/105 housing for 3-phase current
•
CSA certificate German Lloyd approval
<<ÃÒÂÅÐàÍÕ´>> |